2. Two trigger conditions must now be defined; The first trigger condition will be the
input going active, this will activate the macro that will unlock the selected doors.
3. The second trigger condition will be the same input going secure, which in turn will
activate the second macro (to relock the doors again). Only one Global Linkage
Trigger needs to be setup (Global Linkage triggers can have multiple conditions
assigned to them).
Trigger Condition 1
1. Click Add New button from the triggers tab, under Description give it a name.
2. From Condition Type drop-down list select Monitor Point then click Add Condition
button.
3. Highlight the New Condition and rename it, i.e Input - Active.
4. From the Available Message Types list locate the message type Monitor Point -
Alarm, then click Add Messages button.
5. From the Macro drop-down list select the Doors Unlock macro, then save.